LATEST NEWS

LATEST NEWS

Pneumatic Actuated Valve Not Working

5 Common Failures & Fixes

A pneumatic actuated valve that fails to operate is not merely an inconvenience. It is a process interruption, a safety hazard, and an unplanned maintenance event that consumes engineering hours and emergency response resources. When a pneumatic actuated valve is not working, facility managers and plant engineers typically ask: “How do we fix this now?” Few ask the more important question: “Why did this fail, and how do we prevent it from happening again?”

For a complete selection guide to pneumatic actuated valves, visit our main pneumatic actuated valve page.

The answer, backed by field service data from thousands of pneumatic valve installations across Singapore’s process industries, is that most failures fall into five predictable categories. Each category has distinct symptoms, root causes, and proven fixes. Understanding these patterns transforms emergency troubleshooting into systematic prevention.

At Techmatic, we have responded to hundreds of pneumatic actuated valve failures across Jurong Island, Tuas, and Singapore’s water and wastewater facilities. This article covers the five most common failures: stuck spool, low air pressure, solenoid coil failure, positioner drift, and dirty air supply. Each failure is presented with symptoms, causes, and fixes. The article ends with a preventative maintenance checklist to keep your pneumatic actuated valves operating reliably.

Why Pneumatic Actuated Valves Fail in Singapore Facilities

Singapore’s operating environment presents unique challenges for pneumatic actuated valves. High ambient temperatures (30-34°C year-round) accelerate seal degradation and lubricant breakdown. High humidity promotes corrosion in air lines and actuator internals. Process facilities operate continuously—many run 24/7, 365 days per year—leaving no window for unnoticed degradation.

Additionally, compressed air quality in many facilities falls short of ISO 8573-1 standards. Water carryover from poorly maintained dryers, oil carryover from lubrication issues, and particulate matter from corroding pipes all contribute to pneumatic component failures.

The good news: the same five failure modes account for approximately 80% of all pneumatic actuated valve service calls. Diagnose these first, and you will resolve most issues without replacing the entire valve assembly.

Failure #1: Stuck Spool in the Pilot Solenoid Valve

Symptom

The pneumatic actuated valve does not change position when the control signal is applied. The solenoid valve makes an audible click (if equipped with manual override or if the coil is energized), but no air exhausts from the pilot port. The actuator remains in its fail-safe position (either open or closed, depending on actuator type).

In some cases, the valve moves slowly or only partially strokes. In other cases, no movement occurs at all.

Root Cause

The spool inside the pilot solenoid valve (typically a 5/2 or 3/2 way valve) has become stuck due to one of three mechanisms:

  1. Contaminant buildup: Dried compressor oil, rust particles, or pipe scale lodges between the spool and the sleeve, creating friction that exceeds the solenoid’s shifting force.
  2. Sticky residue: In facilities using lubricated air (oil-fog lubricators), the oil can dry or polymerize over time, especially in high-temperature environments. The resulting varnish-like residue locks the spool.
  3. Seal swelling: Certain elastomers (Buna-N, Viton) can swell when exposed to incompatible compressor oils or chemical vapors drawn into the air intake.

Fix

Immediate (system online, emergency repair):

  1. Isolate the air supply to the solenoid valve using the manual shutoff valve (typically located at the valve manifold or actuator air set).
  2. Remove the solenoid pilot valve from the actuator (usually 2-4 screws). Keep track of the sealing gasket or O-rings.
  3. Remove the solenoid coil (the black plastic or metal component with wires). Set aside.
  4. Remove the spool and sleeve assembly from the pilot valve body. Some valves allow spool extraction without special tools; others require a small pick or compressed air blow-through.
  5. Clean the spool and sleeve with a residue-free solvent (isopropyl alcohol or electrical contact cleaner). Do not use WD-40 or penetrating oils—these leave residues that attract more contaminants.
  6. Inspect the spool for scratches or burrs. If damaged, replace the pilot valve assembly.
  7. Reassemble, lubricate with a thin film of lightweight spindle oil (or the manufacturer’s recommended lubricant), and reinstall.
  8. Restore air supply and test.

Permanent (to prevent recurrence):

  • Install a dedicated 5-micron or finer coalescing filter upstream of all solenoid valves.
  • If using lubricated air, verify that the lubricator is not over-feeding (typical setting: 1-2 drops per minute for each standard cubic foot per minute of flow).
  • Consider converting to non-lubricated air (Class 2.2 or better per ISO 8573-1) and using self-lubricating solenoid valves.

Time to fix (on-site): 15-30 minutes for an experienced technician. Parts cost: 

50−200 for a replacement pilot valve assembly.

Failure #2: Low or Inconsistent Air Supply Pressure

Symptom

The pneumatic actuated valve strokes too slowly, fails to stroke fully (e.g., a normally closed valve opens only 50%), or chatters (oscillates) when attempting to change position. The actuator may stall mid-stroke and drift back toward its fail-safe position. When the solenoid de-energizes, the valve may return slowly rather than snapping to position.

In facilities with multiple pneumatic devices, other actuators (other valves, cylinder-driven equipment, air tools) may also show reduced performance.

Root Cause

The actuator requires a minimum supply pressure to generate sufficient force to overcome friction, seat the valve plug, and achieve shutoff. Typical pneumatic actuators require 4-6 bar for proper operation. Low supply pressure can result from:

  1. Compressed air system demand exceeds supply: Multiple large actuators stroking simultaneously can cause a momentary pressure drop. Plant air compressors operating near capacity may not maintain pressure during peak demand.
  2. Undersized or blocked air line: A long, narrow tube (e.g., 50 meters of 6mm OD tube) creates significant pressure drop when the actuator demands high flow. Kinks, crushed tubing, or partially closed manual shutoff valves have the same effect.
  3. Air preparation unit issues: A clogged filter element (particulate loading) or a failed pressure regulator (broken spring, clogged sense port) reduces downstream pressure.
  4. Compressor or dryer problems: Failing compressor unloader, leaking air receiver, or undersized dryer creating freeze-up or excessive pressure drop.

Fix

Immediate (system online, emergency repair):

  1. Install a test pressure gauge immediately upstream of the solenoid valve (or use an existing gauge on the air set). Compare reading to the actuator’s minimum required pressure (stamped on the actuator nameplate).
  2. If pressure is low, adjust the pressure regulator upward (turn clockwise). If no adjustment is possible or the pressure does not increase, bypass the regulator temporarily (connect solenoid directly to main air header) to test. Warning: Do not exceed actuator maximum pressure (typically 8-10 bar).
  3. Check the air filter bowl for visible contamination. If clogged, replace the filter element (do not simply blow it out with compressed air—this pushes captured debris past the element).
  4. Inspect the air tubing from the filter/regulator to the solenoid valve. Remove any kinks or crushing. Replace undersized tubing (minimum 8mm OD for actuators larger than 200 N·m; 6mm acceptable only for very small actuators).

Permanent (to prevent recurrence):

  • Measure pressure at the actuator during peak demand (all valves stroking simultaneously). Size the air supply header and tubing to maintain minimum pressure under worst-case conditions.
  • Install a local air receiver tank (5-10 liters) near large or fast-cycling actuators to provide a local pressure reservoir.
  • Implement pressure monitoring with low-pressure alarm to alert operators before the valve fails to stroke.

Time to fix (on-site): 10-30 minutes for diagnosis; longer if tubing replacement is required. Parts cost: Minimal if only regulator adjustment or filter replacement.

Failure #3: Solenoid Coil Failure (Electrical)

Symptom

The solenoid valve does not click when the control signal is applied. The pneumatic actuated valve does not change position regardless of electrical input. Using a manual override (the small button or screw on the solenoid pilot valve) moves the valve correctly, confirming that the pneumatic side is functional.

The solenoid coil may feel hot to the touch (normal operating temperature is warm but not burning). A completely failed coil may be cold. In some cases, the coil has visible cracks, burn marks, or melted potting compound.

Root Cause

Solenoid coils fail electrically due to:

  1. Voltage mismatch: A 24V DC coil supplied with 110V AC burns out instantly or within minutes. A 110V AC coil supplied with 24V DC will not pull in (but may not be damaged).
  2. Overheating from continuous duty: Some coils are rated for intermittent duty (e.g., 10% duty cycle, meaning energized for 1 minute, de-energized for 9 minutes). Installing such a coil on a valve that remains energized for hours or days causes thermal failure.
  3. Power surge or transient: Lightning strikes, large motor starts, or failed power supplies can send voltage spikes that break down coil insulation.
  4. Moisture ingress: Coils are not hermetically sealed. In humid Singapore environments, condensation inside the coil housing causes corrosion and eventual short circuits.
  5. Mechanical damage: Wire leads pulled too tightly, chafed insulation against metal conduit, or impact damage from nearby maintenance activities.

Fix

Immediate (system online, emergency repair):

  1. Verify that voltage is present at the solenoid coil terminals using a multimeter. Measure both AC and DC (if unsure of coil type). Confirm voltage matches the coil rating (stamped on the coil body).
  2. Measure coil resistance with the power off. Compare to manufacturer specification. A reading of infinite ohms (open circuit) or zero ohms (short circuit) indicates a failed coil.
  3. Remove the failed coil (typically held by a retaining nut or spring clip). Clean any corrosion from the solenoid valve’s armature tube (the metal post that the coil slides over).
  4. Install a replacement coil of exactly the same voltage, frequency (for AC), and wattage. Push fully onto the armature tube and secure.
  5. Restore power and test. The valve should click audibly.

Permanent (to prevent recurrence):

  • Replace intermittent-duty coils with continuous-duty (100% duty cycle) rated coils. The cost difference is small (
  • 10−
  • 10−20) compared to a failure.
  • Install surge suppression devices (varistors or diode suppression for DC, RC snubbers for AC) across the coil terminals, especially if controlled by PLC outputs or relays.
  • Use hermetically sealed or epoxy-encapsulated coils for outdoor or washdown areas.
  • Document coil ratings for all installed valves. Create a spares inventory with the most common coil types (24V DC, 110V AC, 230V AC).

Time to fix (on-site): 10 minutes (with spare coil on hand). Parts cost: 

30−150 depending on coil type and manufacturer.

Failure #4: Positioner Drift or Calibration Shift

Symptom

The pneumatic actuated valve does not track the control signal proportionally. In a 4-20 mA control loop, the valve position may lag behind the signal, overshoot, oscillate, or drift from setpoint over time. The valve may not fully close when the signal is 4 mA (0%) or not fully open at 20 mA (100%).

With the control signal held constant (e.g., 12 mA), the valve position slowly changes (drifts) without any change in the signal. This is particularly dangerous in critical processes.

Root Cause

Smart positioners (digital) and analog positioners (mechanical) drift for different reasons:

For analog (mechanical/I-P) positioners:

  • Nozzle-flapper contamination: Dust, oil mist, or moisture blocks the tiny air bleed nozzle (0.1-0.5 mm orifice). This changes the pilot pressure and shifts the valve position.
  • Feedback spring fatigue: Over time, the spring that senses valve stem position loses tension, changing the calibration.
  • Camming wear: The cam that translates linear or rotary motion to a feedback signal wears, introducing nonlinearity.

For digital (smart) positioners:

  • Auto-calibration drift: Some positioners (particularly lower-cost units) lose calibration after power cycles or after months of operation due to electronic component drift.
  • Pilot stage clogging: Even digital positioners have small pneumatic relay stages (spool or diaphragm) that can clog with contaminated air.
  • Sensor drift: The internal position sensor (potentiometer or Hall effect) may drift with temperature or age.

Both types:

  • Mechanical linkage loose: The connection between the valve stem (or shaft) and the positioner feedback arm has loosened. Set screws, clamps, or levers can slip over time due to vibration.
  • Actuator seal leakage: A worn actuator piston seal or diaphragm leaks air, causing the actuator to slowly drift toward its fail-safe position even with constant positioner output.

Fix

Immediate (system online, emergency repair):

  1. Place the positioner in manual mode (if digital) or bypass the positioner by connecting the control signal directly to a solenoid valve (temporary measure for on/off control only—not for modulating service).
  2. Inspect the mechanical feedback linkage. Tighten any loose screws or clamps.
  3. For analog positioners, remove the nozzle cover and clean the nozzle with a thin wire (0.2 mm) or compressed air. Do not enlarge the orifice.
  4. Perform a positioner autocalibrate (for digital units) or manual recalibration per manufacturer instructions (typically: signal 4 mA, adjust zero; 20 mA, adjust span; repeat 2-3 times).
  5. Stroke the valve fully (0% → 100% → 0%) while observing position feedback. Verify that the valve achieves full travel at both ends.

Permanent (to prevent recurrence):

  • Install a 5-micron or finer air filter dedicated to the positioner supply. Many positioner failures are simply dirty air.
  • Replace analog positioners with digital smart positioners that continuously monitor and correct for drift (e.g., with integrated partial stroke testing and deviation alarms).
  • Implement a calibration schedule. Modulating valves with positioners should be recalibrated every 6-12 months depending on process criticality.
  • If drift recurs frequently, install a valve position monitor (limit switch box with analog feedback) to alarm when deviation exceeds a setpoint (e.g., 5% signal vs. position mismatch).

Time to fix (on-site): 30-60 minutes for recalibration; longer if linkage repair is needed. Parts cost: Minimal if only cleaning or calibration; 

500−2,000 for analog to digital positioner upgrade.

Failure #5: Dirty or Wet Air Supply

Symptom

This is the root cause behind many of the previous failures, but it deserves its own category because the symptoms are distinctive. Common indicators include:

  • Erratic valve operation: The valve strokes inconsistently—sometimes fast, sometimes slow, sometimes not at all—with no pattern.
  • Water spitting from exhaust ports: Liquid water sprays out of the solenoid valve exhaust when the valve shifts.
  • Rust-colored residue on valve stems, actuator exhaust ports, or inside solenoid valves.
  • Freezing at exhaust ports: In high-humidity environments, rapid expansion of wet air can cause localized freezing (ice crystals visible at exhaust). This occurs even in Singapore’s tropical climate when dew point is poorly controlled.
  • Frequent solenoid valve sticking (as described in Failure #1) despite recent cleaning.

Root Cause

Compressed air quality in many facilities falls below ISO 8573-1 Class 3 (maximum particle size 5 microns, maximum pressure dew point -20°C, maximum oil content 1 mg/m³). Common problems include:

  1. Inadequate drying: Refrigerated air dryers undersized for the compressor’s flow rate, or dryers operating with dirty condensers (common in Singapore’s dusty outdoor environments). Result: air reaches dew point above ambient temperature, and water condenses in the pipes.
  2. Lack of filtration: No coalescing filter installed, or filter element not changed for years. Oil and water aerosols pass through to downstream components.
  3. Corroding air piping: Old galvanized steel or black iron pipes rust internally, generating fine rust particles that travel to solenoid valves and positioners.
  4. Compressor oil carryover: Rotary screw compressors with failing separators pass oil mist into the air system.

Fix

Immediate (system online, emergency repair):

This is not a quick fix. Dirty air supply affects all downstream pneumatics. Emergency measures include:

  1. Install a temporary high-efficiency coalescing filter (0.01 micron) immediately upstream of the affected valve. This is a band-aid, not a solution.
  2. Drain water from air receivers, drip legs, and low points in the piping system. Many facilities have automatic drains that have failed or manual drains that no one touches.
  3. Replace clogged filter elements at the air preparation unit (filter/regulator) serving the valve.

Permanent (to prevent recurrence):

  1. Audit compressed air quality to ISO 8573-1. Measure particle count, pressure dew point, and oil content at the point of use. In Singapore, the ambient temperature is 30°C, so pressure dew point must be below 30°C to prevent condensation. For reliable operation, target -20°C or lower.
  2. Upgrade air drying: If using a refrigerated dryer, verify it can achieve a pressure dew point of 3-10°C (marginal for Singapore’s humidity). Consider adding a desiccant dryer downstream to achieve -40°C dew point.
  3. Replace corroding air piping with copper, stainless steel, or aluminum. For existing systems, install coalescing filters at each branch or at each piece of equipment.
  4. Implement a filter maintenance schedule. Coalescing filter elements must be changed every 6-12 months regardless of visible condition. Differential pressure gauges on filter housings help schedule changes.
  5. Switch to non-lubricated air. Remove all lubricators from the system. Use actuators and solenoid valves designed for unlubricated service (most modern units are). Lubricated air creates sticky residues that attracts contaminants.

Time to fix (on-site): Hours to days for emergency mitigation; weeks to months for permanent system upgrade. Parts cost: 

100−500 for local filtration; 

5,000−50,000 for system-wide air treatment upgrade.

Preventative Maintenance Checklist for Pneumatic Actuated Valves

Preventing the five failures above requires a systematic maintenance approach. Use this checklist for monthly, quarterly, and annual tasks.

Monthly Tasks (Operator Rounds)

Task Acceptance Criteria Action if Failed
Listen for air leaks No hissing sounds at fittings, tubing, or solenoid exhaust ports Tighten fittings; replace damaged tubing; repair leaking solenoid
Observe valve stroke time Valve opens and closes within normal time range (record baseline) Investigate if stroke time increases by >25%
Check filter bowls No visible water or oil accumulation Drain bowl; investigate air dryer performance
Verify manual override operation Solenoid manual override moves valve freely Clean or replace solenoid pilot valve
Listen for positioner cycling Positioner should not continuously cycle (hunt) at steady signal Recalibrate positioner; check linkage

Quarterly Tasks (Maintenance Technician)

  • Check air supply pressure at each valve under static (no stroking) and dynamic (stroking) conditions. Pressure should not drop more than 0.5 bar during stroke.
  • Inspect solenoid coil temperature using infrared thermometer. Compare to baseline. Coils exceeding 70°C surface temperature may be failing.
  • Clean solenoid valve exhaust ports. Remove any debris, rust, or sticky residue.
  • Test positioner calibration at 0%, 50%, and 100% signal. Record deviation. Recalibrate if deviation exceeds 3% for non-critical valves, 1% for critical valves.
  • Check feedback linkage set screws and clamps for tightness.
  • Replace air filter elements (at air preparation unit) every 3 months regardless of visible condition. Use a calendar schedule.

Annual Tasks (Planned Shutdown)

  • Bench test solenoid valve. Remove pilot valve, apply controlled air pressure and electrical signal. Verify shifting pressure and exhaust flow.
  • Replace solenoid pilot valve seals (if service kit available). O-rings and gaskets degrade over time regardless of use.
  • Inspect actuator internals. Remove actuator end caps (where possible). Check piston seal or diaphragm for wear, cracking, or leakage.
  • Lubricate actuator per manufacturer recommendation (only if using lubricated air system). Most modern actuators are pre-lubricated for life.
  • Replace positioner pilot stage filter. Smart positioners have small inlet filters that must be changed annually.
  • Validate fail-safe operation. Remove air supply and electrical signal. Verify valve moves to correct fail-safe position (open or closed) and stays there.

Spare Parts Inventory Recommendations

For a facility with 20-50 pneumatic actuated valves, maintain the following minimum spares:

Part Quantity Notes
Solenoid coils (most common voltage) 5 each of 24V DC, 110V AC Stock based on installed base
Complete solenoid pilot valves (5/2 or 3/2) 3-5 units Quicker to replace than rebuild
Air filter elements (various micron ratings) 10-20 Changed quarterly
Pressure regulator (generic, 0-8 bar range) 2 Can substitute for failed unit
Tubing and fittings (6mm, 8mm, 10mm) Assorted lengths and elbow/straight fittings For emergency repairs
Positioner (digital, programmed for common valve type) 1-2 Program spares before storage
Actuator seal kits (common sizes) 2-3 kits per actuator type Long lead time items

External References and Live Citations

Industry standards and technical guidelines confirm the failure modes and fixes described above:

Recommendation: Consult a Qualified Supplier

Pneumatic actuated valve troubleshooting is systematic, but not every facility has the time, tools, or trained personnel to diagnose and repair failures quickly. For critical processes, standby support is essential.

At Techmatic, we provide pneumatic actuated valve sales, installation, commissioning, and emergency repair services across Singapore. Our team carries common spare parts (coils, pilot valves, positioners, seal kits) for rapid response. We can also perform compressed air quality audits and recommend upgrades to prevent recurring failures.

Contact Techmatic for pneumatic actuated valve support

Frequently Asked Questions (FAQs)

1. How can I tell if my pneumatic actuated valve failure is electrical or pneumatic?

Use the manual override on the solenoid pilot valve. If the valve strokes correctly when you push the manual override button (or turn the manual screw), the pneumatic side is functional. The problem is electrical (coil, wiring, PLC output) or the solenoid pilot spool is stuck. If the manual override does not move the valve, the problem is pneumatic (low air pressure, failed actuator, blocked tubing).

2. What is the typical lifespan of a pneumatic actuated valve?

With clean, dry air and proper maintenance, the actuator itself can last 10-20 years. Solenoid valves typically last 5-10 years or 1-5 million cycles. Positioners (digital) last 5-10 years; analog positioners last 10-15 years but drift more. The valve body (ball, butterfly, globe) lifespan depends on process conditions—corrosive or erosive services may fail much faster.

3. Do I need to lubricate the air supply to my pneumatic actuator?

Most modern actuators (from major manufacturers like Rotork, Bray, Kinetrol, and others) are designed for non-lubricated service. They contain internal bearing and seal materials that run dry. Adding oil to the air supply creates sticky residues that attract dust and can cause solenoid valve sticking. Unless the actuator manufacturer explicitly requires lubricated air (older designs or special materials), run dry.

4. Why does my pneumatic valve stroke slower in the afternoon than in the morning?

This is almost always wet air. In the morning, the air system has higher relative humidity. As the day warms up, moisture evaporates and carries over to the valve. The water in the air causes freezing at the solenoid exhaust port (due to rapid expansion cooling) or simply creates viscous drag on the spool. Check your air dryer performance—it should maintain pressure dew point below ambient temperature at all times.

5. Can I replace a failed solenoid coil without removing the entire solenoid valve?

Yes, for most solenoid valves. The coil is a separate component that slides over the armature tube. Simply remove the retaining nut or spring clip, lift off the old coil, clean the armature tube, and slide on the new coil. Ensure the new coil has the exact same voltage, frequency, and wattage. No need to break pipe connections or remove the valve body.

6. What is the cost difference between a standard and a smart positioner?

A standard analog (I/P) positioner costs 

300−300−800. A digital smart positioner costs 

800−800−2,500. The higher cost is justified by diagnostic capabilities (partial stroke testing, deviation alarms, travel limit monitoring), auto-calibration, and lower air consumption (smart positioners only output air when needed; analogs bleed continuously). For critical modulating service, smart positioners pay back through reduced maintenance and avoided process upsets.

7. How do I know if my air dryer is working correctly?

Measure pressure dew point at the dryer outlet using a portable dew point meter (hire from instrument supplier). For Singapore facilities, a properly functioning refrigerated dryer should achieve 3-10°C pressure dew point. A desiccant dryer should achieve -40°C or lower. If the meter shows dew point above ambient temperature (30°C), water is condensing in your air lines. Also check the dryer’s condensate drain—if no water drains, the drain may be clogged or failed.

8. What should I do if my valve positioner shows “deviation alarm” but the valve seems to work fine?

Deviation means the position sensor reads a different valve position than the control signal requests. Small deviations (1-3%) are normal during stroking. Persistent deviation at steady signal indicates calibration drift, loose linkage, or failing actuator seals. Do not ignore the alarm—it will worsen. Perform a positioner autocalibration and check mechanical linkage tightness. If the alarm returns within weeks, inspect the actuator for seal leakage.

Further Reading from Techmatic

For more technical insights into valve selection, actuation, and maintenance in Singapore facilities, explore these related articles from the Techmatic news section:

Final Summary

Failure Primary Symptom Most Likely Fix Prevention
Stuck spool Solenoid clicks but valve does not move Clean or replace pilot valve spool Install 5-micron air filter; avoid oiled air
Low air pressure Slow or partial stroking Increase regulator setting; check filter Size air supply for peak demand
Coil failure No click, manual override works Replace coil with matching voltage Use continuous-duty coils; add surge suppression
Positioner drift Valve does not track control signal Recalibrate; tighten linkage Upgrade to digital positioner; annual calibration
Dirty/wet air Erratic operation; water from exhaust Install coalescing filter; drain system Audit air quality; upgrade dryer

Final recommendation: Most pneumatic actuated valve failures are preventable. Clean, dry compressed air (ISO 8573-1 Class 1.4.1 or better) eliminates 60% of failure modes. A scheduled preventative maintenance program (monthly operator checks, quarterly technician inspections, annual overhauls) catches the remaining failures before they cause unplanned shutdowns. When failures do occur, diagnose systematically: pneumatic first (air supply, pressure), then mechanical (spool, linkage), then electrical (coil, signal). Keep spare coils, pilot valves, and filter elements on hand. For critical valves, consider duplex solenoid configurations or smart positioners with deviation alarms. When in doubt, consult a qualified supplier like Techmatic with site-specific data.